| S6029 Micro-differential Pressure Transmitter? |
| |
 |
|
| |
S6029 Mico-differential pressure transmitter is designed to measure the difference between two sensed pressures to produce 0-10VDC proportional output.
The differential pressure, as sensed by the sensing ports, is applied to both sides or a mass air flow sensor, directed across the surface of the sensing element.
The output voltage varies in proportion to the differential temperature of sensing elements as a consequence of increasing/decreasing the mass air flow through the inlet and outlet ports caused by sensed differential pressure. |
|
| |
Specification |
|
| |
Output Signal |
: |
0-10VDC linear to diffferential pressure |
|
| |
Ambient Op. Limits |
: |
0-60¡ãC, RH 10-90%, non condensing |
|
| |
Power Consumption |
: |
350mW (24mA at 15VDC) |
|
| |
Enclosure protection |
: |
IP20 |
|
| |
Max Pressure |
: |
500 mbar |
|
| |
Accuracy Linear |
: |
Zero point - <¡À0.7% FS
output 0-1mbar - <¡À1.0% FS
Linearity inclusive - <¡À1.0% FS
hysteresis 0-1mbar - <¡À2.0% FS |
|
| |
Material |
: |
Seal : Viton, EPDM, NBR, Silicone, CR |
|
| |
|
: |
Diaphragm : 2-component Silicone LSR |
|
| |
Temperature range |
: |
Medium and ambient : 0 - 70¡ã
Storage : -10 - 70¡ã
TC Zero point with linear
output: < ¡À 0.04% fs/¡ãC
Root-extracted output:
< ¡À0.06 ?PFS/P in % fs/¡ãC
TC Sensitivity : < ¡À 0.02% fs/¡ãC |
|
| |
Dynamic response |
: |
Suitable for dynamic
measurements <10ms
Load change < 10Hz
1 mbar fs : <0.2%FS
3-50 mbar fs: <0.1%FS
|
|
| |
Load impedance |
: |
3-wire cable:
0-10 V>10k Ohm
0 - 20 mA < 400 Ohm
4 - 20 mA < 400 Ohm
2-wire cable
4 - 20 mA (supply voltage - 11V / 0.02A) [Ohm] |
|
| |
Current consumption |
: |
3-wire cable
0 - 10V < 10 mA
0 - 20 mA < 30 mA
4 - 20 mA < 30 mA
2-wire cable
4 - 20 mA |
|
| |
Shipping Weight |
: |
200g |