| S6022- Flow Switch? |
| |
 |
|
| |
The S6022 flow switch respond to low fluid flow rate in applications with pipe sizes under 1¡± to 3¡± size. |
|
| |
The S6022 flow switch use a variety of paddle sizes to respond to fluid flow rates in applications with pipe size greater than 1¡± trade size. |
|
| |
These paddle-type flow switches are designed for pipe fluid flow indication. Suitable fluids include water, ethylene glycol solutions and fluid not harmful to brass or phosphor bronze or classified as hazardous fluid. |
|
| |
A 3-piece stainless steel paddle kit is included allowing effective installation in variety of pipe size and fluid flow conditions. |
|
| |
Single-pole, Double-throw (SPDT) open-low versions of these flow switches are available. |
|
| |
Specification |
|
| |
Contact Capacity |
: |
AC 220V 10A |
|
| |
Valve size |
: |
3¡± |
|
| |
Max. Paddle Length |
: |
6¡± (1 - 6¡± trimmable) |
|
| |
Connector |
: |
1¡± - 11.5¡± (NTP) |
|
| |
Max pressure |
: |
18 bar |
|
| |
Median Ambient |
: |
0 - 120¡ã |
|
| |
Temperature Allowed |
|
| |
Max Temperature |
: |
-30 - 120¡ã |
|
| |
Protection |
: |
IP 65 |
|
| |
Range of flow |
: |
1¡± Pipe Min Flow decrease: 2.5
Min Flow increase: 4.2
Max Flow decrease: 8.5
Max Flow increase: 8.8
2¡± Pipe Min Flow decrease: 9.5 Min Flowincrease: 13.7
Max Flow decrease: 27
Max Flow increase: 29
3¡± Pipe Min Flow decrease: 19
Min Flow increase: 27.5
Max Flow decrease: 50
Max Flow increase: 53
|
|
| |
Shipping weight |
: |
700g |
|
| |
Mounting |
|
| |
Install the switch so that the flow of fluid is in the direction of the arrow on the switch casing.
Use a pipe union on each side of the flow switch to allow easy removal or replacement.
Do not allow the pipe to extend too far into the flow switch casing.
Use pipe thread sealer on male threads only.
Do not remove the cover gasket or the wire grommet from the conduit opening. |
|
| |
For 1¡± pipe installation, mount the S6062 flow switch in a standard 1¡± x 1¡± x ¡° tee. For larger sizes of pipe, use a reducing tee to keep the flow switch close to the pipe and provide adequate paddle length in the flow stream. Mount the flow switch so the terminals or wire leads are easily accessible for wiring. Screw the flow switch in position so the flat of the paddle is at a right angle to the flow. The arrow on the side of the case must point in the direction of the flow. |