| SD6200 Heat Detector for Fixed Temperature |
| |
 |
Technological parameters |
|
| · Operating voltage: 19V~24V |
| · Temperature-sensing style: fixed temp. |
| · Operating current: ≤0.5mA |
| · Protect area: 40 m2 |
| · Alarm current: ≤3mA |
| · Ambient temperature : 0℃~80℃ |
| · Ambient humidity:≤95% no-condensation |
| · Alarm temperature: |
| |
degree 54℃~62℃
Ⅱdegree 62℃~70℃
Ⅲdegree 70℃~78℃ |
| · Overall size: Φ104mm |
| · Installation style: bi-bus, no-polarity |
| |
SD6200 heat detector for fixed temperature utilizes the sensibility of semiconductor’s thermal element for temperature to check up ambient temperature, meanwhile it converts the detected temperature into analogue signal to fire alarm controller. When the temperature achieves the alarm value, the fire alarm controller sends the alarm signal.
|
|
| |
Characteristics |
|
| |
Communication circuit and detection circuit merge into an organic whole, and it needn’t coding base.
|
|
| |
Set three degree sensitivity according to ambient environment. |
|
| |
High stability, low misstatement rate and non-weather influence. |
|
| |
Application spot |
|
| |
relative humidity often excesses 95%, those places where no-smoke fire possibly happens and exist plenty of dust |
|
| |
The places where there are smog and vapor in normal situation |
|
| |
Kitchen, boiler room, generator room, drying room |
|
| |
Garage, smoking room |
|
| |
The hall and public places where it isn’t convenient to install smoke detector |